Output Programming Selection Table:
Outputs must be programmed independently (OUT1 - OUT4)
Function Switch Positions Descriptions
ON OFF
InputtoOutputFollower
Mode
1 2,3 Outputfollowssignalitreceivesfromthecorrespondinginput(i.e.
FACPSyncmodule-maintainssynchronizationof
notificationappliancecircuit).
TemporalCode3Mode 3 1,2 EnablesTemporalCode3signalgenerationoutput.
Thismodewillacceptasteadyorapulsinginput.
SteadyMode 1,2,3 Asteadyoutputsignalwillbegenerated.
Thismodewillacceptsteadyorpulsinginput.
For the above modes Dip Switch 4 determines which Input controls the corresponding output:
Switch 4 in the ON position causes output(s) to be controlled by input 1.
Switch 4 in the OFF position causes output(s) to be controlled by input 2.
Sync Mode Selection Table:
Function
Switch Positions
Descriptions
ON OFF
AmsecoSync
Mode*
1,3,
4
2
ThismodeisdesignedtoworkwiththeAmsecoseriesofhorns,strobes,and
horn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,
synchronizingtheflashtimingofthestrobe,andsilencingthehornsofthehorn/
strobecombinationoveratwo-wirecircuitwhileleavingstrobesactive.
Faraday
SyncMode*
2,4 1,3
ThismodeisdesignedtoworkwiththeFaradayseriesofhorns,strobes,andhorn/
strobestoprovideameansofsynchronizingtheTemporal-codedhorns,synchro-
nizingtheflashtimingofthestrobe,andsilencingthehornsofthehorn/strobe
combinationoveratwo-wirecircuitwhileleavingstrobesactive.
Gentex
®
SyncMode*
Gentexisaregisteredtrademark
ofGentexCorporation.
1,2,
3,4
ThismodeisdesignedtoworkwiththeGentex
®
seriesofhorns,strobes,andhorn/
strobestoprovideameansofsynchronizingtheTemporal-codedhorns,synchro-
nizingtheflashtimingofthestrobe,andsilencingthehornsofthehorn/strobe
combinationoveratwo-wirecircuitwhileleavingstrobesactive.
SystemSensor
®
SyncMode*
SystemSensorisaregistered
trademarkofHoneywell.
1,2,4 3
ThismodeisdesignedtoworkwiththeSystemSensor
®
seriesofhorns,strobes,
andhorn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,
synchronizingtheone-secondflashtimingofthestrobe,andsilencingthehornsof
thehorn/strobecombinationoveratwo-wirecircuitwhileleavingstrobesactive.
CooperWheelock
®
SyncMode*
CooperWheelockisa
registeredtrademarkof
CooperWheelock.
2,3,4 1
ThismodeisdesignedtoworkwiththeCooperWheelockseriesofhorns,strobes,
andhorn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,
synchronizingtheone-secondflashtimingofthestrobe,andsilencingthehornsof
thehorn/strobecombinationoveratwo-wirecircuitwhileleavingstrobesactive.
Note:TheAL842ULADAwillonlysynchronizehorns,horn/strobesandstrobesthatcontainsynchronizationcapability.
Contactsignalmanufacturerformoredetailedinfo.Thesamesynchronizationmodemustbeselectedforalloutputs.
Note: It is required to control visual notification appliances (strobes) via input 1 [IN1] and audible notification
appliances (horns) via input 2 [IN2]. This allows audible notification appliances (horns) to be silenced while
visual notification appliances (strobes) continue to operate.
Amount of Notification Appliances per NAC:
Amseco 27perNAC*
SystemSensor® 32perNAC*
Faraday 39perNAC*
CooperWheelock® 32perNAC*
Gentex® 32perNAC*
*Not to exceed a maximum of 2.5 amp per NAC.
AL842LGK Board
(Output Dip Switches)
INPUT SELECT
TEMPORAL
STROBE SYNC
IN>OUT SYNC