Rev. 052313AL1002ULADANAC Power ExtenderInstallation Guide(See Application Guide for additional information)Altronix Corp.140 58th St. Brooklyn, NY
- 10 - AL1002ULADAAppendix A - UL Listed Compatible DevicesA.1 Four (4) Wire Smoke DetectorsTableA-1belowlistsfour(4)wiresmokedetectorscompat
AL1002ULADA - 11 -A.1 Four (4) Wire Smoke Detectors (cont.)Smoke Detector/BaseDetector TypeMax StandbyCurrent (mA)AlarmCurrent (mA)SystemSensor4W-
- 12 - AL1002ULADAEnclosure Dimensions (H x W x D approx.):15.5”x12”x4.5”(393.7mmx304.8mmx114.3mm)MEMBERAltronixisnotresponsibleforanyt
- 2 - AL1002ULADA Agency Listings:• ULListedControlUnitsforFireProtective SignalingSystems(UL864).• MEA-NYCDepartmentofBuilding
AL1002ULADA - 3 -Power Supply Specifications:AC Input:120VAC60Hz,5amp.Output:Four(4)regulatedsupervisedNACoutputcircuits,24VDC,2.5ampmax
- 4 - AL1002ULADA6. ConnectFACPoutputtodesiredAL800LGKlogicboardinputs,andnotificationappliancestodesiredAL800LGK logicboardout
AL1002ULADA - 5 -Amount of Notification Appliances per NAC:Amseco 27perNAC* SystemSensor® 32perNAC*Faraday 39perNAC* CooperWheelock® 32perN
- 6 - AL1002ULADATerminal Identification Table:Power Supply Board*Terminal Legend Function/DescriptionL,N Connect120VACtotheseterminals:Ltoh
AL1002ULADA - 7 -ExternalJacketedShieldIncorrect WireHandlingCorrect WireHandlingPull backexternal jacketedshield approx. 1/2”.WireInsulationSolid Co
- 8 - AL1002ULADAOptional hookups:1- BatteryandACmonitoring:ACorBatteryFailconditionwillcausethecommontroubleinput[C“FAULT”NC]to
AL1002ULADA - 9 -Battery Calculation WorksheetDeviceNumber of DevicesCurrent per DeviceStand-by CurrentAlarm CurrentForeachdeviceusethis