Altronix AL802ULADAJ Guia de Instalação Página 9

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 12
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 8
AL802ULADAJ - 9 -
Battery Calculation Worksheet
Units are capable of recharging 40 AH battery max. If total ampere - hour required exceeds 40 AH,
decrease AUX current to provide enough stand-by time for the application.
Device
Number of
Devices
Current per Device
Stand-by
Current
Alarm
Current
For each device use this formula: This column x This column = Equals Current per number of devices.
AL802ULADAJ
(Current draw from battery)
1
Stand-by: 90mA 90mA
Alarm:
175mA 175mA
A AL802 Current
90mA 175mA
Auxiliary Devices Refer to device manual for current ratings.
Alarm/Stand-by mA mA mA
Alarm/Stand-by mA mA mA
Alarm/Stand-by mA mA mA
B Auxiliary Devices Current (must not exceed 1 amp)
Refer to device manual for current ratings.
Alarm: mA 0mA mA
Alarm: mA 0mA mA
Alarm: mA 0mA mA
Alarm: mA 0mA mA
C
Notification Appliances Current must not exceed 8 amp (8000mA) 0mA mA
D
Total alarm current mA mA
E
Total current ratings converted to amperes (line D x .001) A A
F
Number of standby hours (24 for NFPA 72, Chapter 1, 1-5.2.5). H
G
Multiply lines E and F. Total stand-by AH AH
H
Alarm sounding period in hours.
(For example, 5 minutes = .0833 hours.)
H
I
Multiply lines E and H. Total alarm AH AH
J
Add lines G and I. Total stand-by and alarm AH AH
K
Multiply line J by 1.30.
(30% extra insurance to meet desired performance)
Total ampere - hours required
AH
Vista de página 8
1 2 3 4 5 6 7 8 9 10 11 12

Comentários a estes Manuais

Sem comentários