- 4 - AL600ULX Series
 ForFireAlarmapplicationstheoutputsare“SpecialApplications”only,seelist(refer to Appendix A, pg. 6).
3. Set the unit to the desired DC output voltage by setting SW1 (Fig. 1b, pg. 3) to the appropriate position
(Power Supply Voltage Output Selections Chart, pg. 2).
4. Measureoutputvoltagebeforeconnectinganydevicestoensureproperoperation.Improperorhighvoltagewill
damage these devices. When servicing the unit, AC mains should be removed.
5. Connect device(s) to be powered:
a. ForAL600ULX(R)PowerSupplyconnectdevicestoterminalsmarked[+DC-](Fig. 1, pg. 3).
b. ForotherPowerDistributionModelsconnectdevicestobepoweredtoterminalpairs1to4marked
[1P & 1N thru 4P & 4N] (Fig. 2a & 2b, pg. 5) or 1 to 8 marked [1P & 1N thru 8P & 8N] (Fig. 3a & 3b, pg. 5)
carefully observing correct polarity.
6. For Access Control applications, batteries are optional. When batteries are not used, a loss of AC will result in the
loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type.
7. Connectappropriatesignalingnotificationdevicestoterminalsmarked[ACFAIL&BATFAIL](Fig. 1, pg. 3)
supervisory relay outputs.
Note:Whenusedinfirealarmoraccesscontrolapplications,“ACFail”relayshouldbeutilized
tovisuallyindicatethatACpowerison.Todelayreport6hourscut“ACDelay”jumper(Fig. 1a, pg. 3).
8. Please insure that the cover is secured with the provided Key Lock.
Wiring:
Use 14 AWG or larger for all power connections.
Note: Take care to keep power-limited circuits separate from non-power limited wiring (115VAC, Battery).
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level
(Power Supply Voltage Output Specifications Chart, pg. 3).
Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage both at
batteryterminalandattheboardterminalsmarked[+BAT–]toinsurethereisnobreakinthebattery
connection wires.
Note:Maximumchargingcurrentunderdischargesis0.7amp.
Note: Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed.
LED Diagnostics:
Power Supply Board
Red (DC) Green (AC) Power Supply Status
ON ON Normal operating condition.
ON OFF Loss of AC, Stand-by battery supplying power.
OFF ON No DC output.
OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
Red (Bat) Battery Status
ON Normal operating condition.
OFF Battery fail/low battery.
Power Distribution Module
Green (AC) Power Distribution Module Status
ON Normal operating condition.
OFF No Power Output.