*Note:TheAL602ULADAwillonlysynchronizehorns,horn/strobesandstrobesthatcontainsynchronizationcapability.
Contactsignalmanufacturerformoredetailedinfo(see Appendix A.4, pg. 12).Thesamesynchronizationmodemustbe
selectedforalloutputs
Amount of Notification Appliances per NAC:
Amseco 27perNAC*
SystemSensor® 32perNAC*
Faraday 39perNAC*
CooperWheelock® 32perNAC*
Gentex® 32perNAC*
*Not to exceed a maximum of 2.5 amp per NAC.
Terminal Identification Table:
AL800LGK9E Logic Board
Terminal
Legend
Function/Description
IN1+,IN1-
IN2+,IN2-
(Supervised)
Theseterminalsconnecttothe24VDCFACPnotificationappliancecircuitoutputs.
(ClassA,StyleZorClassB,StyleW,X,Y)Inputtriggervoltageis8-33VDC@5mAmin.
Terminalpolarityisshowninalarmcondition.Duringanalarmconditiontheseinputswillcause
theselectedoutputschosentodrivenotificationappliances.Thedesignatedoutputsaresetbyoutput
switches[OUT1throughOUT4](Output Programming Selection Table, pg. 4). Atroubleconditionon
anoutputloopwillcausethecorrespondinginputtotriptheFACPbyopeningtheFACPloop.An
alarmconditionwillalwaysoverridetroubletodrivenotificationappliances.
RET1+,RET1-
RET2+,RET2-
(Supervised)
For(ClassA,StyleZhookupstheseterminalpairsreturntoFACPNAC1and/orNAC2.For
ClassB,StyleW,X,YhookupstheFACPEOLresistorfromtheNAC1and/orNAC2outputsare
terminatedattheseterminals.
C“DRY1”NC
C“DRY2”NC
(Dryinputtrigger)
Anopenacrosstheseinputs,willcausetheselectedoutputschosentodrivenotificationappli-
ances.Thedesignatedoutputsaresetbyoutputswitches[OUT1throughOUT4](Output
Programming Selection Table, pg. 4).Notetheseinputsareunidirectionalandwillnotreporta
troubleconditiontotheFACP.
+OUT1--
+OUT2--
+OUT3--
+OUT4--
(Supervised)
Notificationappliancesareconnectedtotheseregulatedoutputs (see 02 Application Guide pg.
2-4). Eachpower-limitedoutputwillsupply2.5amp.Two(2)outputsmaybeconnectedinparallel
foramaximumNACoutputcapabilityof4amp.Totalsupplycurrentis6.5amp(see note below).
Outputsarecontrolledbydesignatedinput1[IN1]orinput2[IN2](Output Programming Selection
C“FAULT”NC
(Common
troubleinput)
Anopencircuitacrossthispairofterminalswillcause[IN1andIN2]tosimultaneouslysignala
troubleconditionbacktotheFACP(TypicallyusedtoreportACorBATFail).(form“C”contact
1amp/28VDC)(Fig. 2, pg. 7).
NC,C,NO
(Common
troubleoutput)
Thesearedrycontacttroubleoutputsthatfollowanygeneralloop/systemtroubleconditions.
(Typicallyusedtotriggeradigitalcommunicatororotherreportingdevice).
(form“C”contact1amp/28VDC0.35PowerFactor)(Fig. 2, pg. 7) .
--AUX+ Thisseparate1ampmaxauxiliarySpecialApplicationPoweroutputcircuitistypicallyusedto
power4-wiresmokedetectors.Seeattachedlistofdevices(Appendix A, pgs. 10-12).
+DC-- 24VDCfrompowersupply.
Note: Unit is equipped with 1 amp max. auxiliary output: “AUX” will remain battery backed up during power
outage. For loads connected to “AUX” please refer to battery “Stand-by Specifications” pg. 3 for ratings. When
loads are connected to “AUX” output during alarm condition, the remaining outputs may not exceed 6.5 amp
total alarm current (example: AUX = 1 amp, outputs up to 5.5 amp).
AL602ULADA - 5 -