PM212 - Supervised Linear
Power Supply / Charger
Overview:
PM212 supervised linear power supply/charger converts a low voltage “AC” input to a filtered and regulated
12VDC, 1 amp continuous power limited output.
Specifications:
Input:
16VAC/20VA
Output:
12VDC output
1 amp continuous supply current
Filtered and electronically regulated output
Thermal and short circuit protection with auto reset
Battery Backup:
Built-in char
ger for sealed lead acid or gel type batteries
Automatic switchover to stand-by battery when AC Fails
PTC battery protection.
Supervision:
AC fail supervision (form “C” contacts)
Low battery supervision (form “C” contacts)
Additional Features:
AC input and DC output LED indicators
Includes batter
y leads
Board Dimensions: 5.25"L x 2.75"W x 1.5"H (approximate)
Installation Instructions:
1. Connect proper transformer (16VAC, 20VA) to terminals marked [AC].
2. Measure output voltage before connecting devices. This helps avoid potential damage.
3. Connect devices to be powered to terminals marked [- DC +], carefully observing polarity.
4. When the use of stand-by batteries are desired, they must be lead acid or gel type.
Connect battery to terminals marked [ - BAT +] on the unit (battery leads included).
Note: When batteries are not used a loss of AC will result in the loss of output voltage.
5. Connect appropriate signaling notif
ication devices to AC Fail & Low battery supervisory relay output
terminals marked [N.C., C, N.O.].
Note: During normal operation (A
C and battery connected). the N.C. and C relay contacts will be in
the closed position and the N.O. and C relay contacts will be in the open position.
These contacts are rated at 2 amp, 120VAC/28VDC
AC
DC
AC FAIL
LOW BAT
BKLYN., NY 11220
MADE IN U.S.A.
RL2
RL1
PTC1
IC1
C1
NC C NO
NC C NO
Vista de página 0
1 2

Resumo do Conteúdo

Página 1 - Power Supply / Charger

PM212 - Supervised LinearPower Supply / ChargerOverview:PM212 supervised linear power supply/charger converts a low voltage “AC” input to a filtered a

Página 2 - Terminal Identification:

Terminal Identification:Terminal Function/DescriptionLegendAC / AC Low voltage AC input (16VAC / 20VA mi.). Altronix part # TP1620.+ DC -12VDC @ 1 amp