- 4 - Maximal11D/Maximal33D/Maximal55D/Maximal77D/Maximal75D Access Power Controllers (PTC)
• RedLEDsonACM8CBboardindicateindividualoutputsaretriggered(relaysenergized).
• FireAlarmdisconnect(latchingornon-latching)isindividuallyselectableforanyorallofthesixteen(16)outputs.
Fire Alarm disconnect input trigger options:
a) Normally open (NO) or normally closed (NC) dry trigger input.
b) Polarity reversal input from FACP signaling circuit.
• GreenLEDonACM8CBboardindicatesFACPdisconnectistriggered.
• FACP output relay indicates that FACP input is triggered (form “C” contact rated @ 1 amp/28VDC not evaluated by UL).
• Powersupplyinputoptions:
a) Factory installed power supplies provide common power for both ACM8CB boards and all connected
access control devices.
b) An optional UL Listed power-limited external access control power supply may be connected to isolate
the ACM8CB boards from the access control devices (only applicable on Maximal11D).
• ACM8CBboardmainfusesarerated@10amp.OutputPTCsarerated@2amp.
• Built-inchargerforsealedleadacidorgeltypebatteries.
- Maximum charge current is 0.7 amp for AL400ULXB, AL600ULXB and AL1012ULXB power supply boards.
- Maximum charge current is 3.6 amp for AL1024ULXB power supply board.
• Automaticswitchovertostand-bybatterywhenACfails.
• Zerovoltagedropwhenunitswitchesovertobatterybackup(ACfailurecondition).
• Shortcircuitandthermaloverloadprotectionwithautoreset.
• GreenACinputandredDCoutputLEDindicatorsonpowersupplyboard(s).
• ACfailsupervision(form“C”contactrated@1amp/28VDC).
• Batteryfailandbatterypresencesupervision(form“C”contactrated@1amp/28VDC).
• Enclosureaccommodatesuptofour(4)12VDC/12AHbatteries.
Enclosure dimensions: 26” (660.4mm) x 19” (482.6mm) x 6.25” (158.75mm)
MaximalD Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and
authorities having jurisdiction. Product is intended for indoor use only.
Power Supply Board LED Diagnostics (pg. 6)
Access Power Controller LED Diagnostics (pg. 6)
Power Supply Board Terminal Identification (pg. 6)
Access Power Controller Terminal Identification (pg. 7)
Power Supply Board Stand-by Battery Specifications (pg. 7)
Power Supply Board Output Voltage Settings (pg. 8)
Access Power Controller Typical Application Diagram (pg. 8)
FACP/Optional Power Supply Hook-up Diagrams (pg. 16)
1. Mount unit in desired location. Mark and predrill holes in the wall to line up with the top three keyholes in the
enclosure. Install three upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s
upper keyholes over the three upper screws, level and secure. Mark the position of the lower three holes.
Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes
over the three upper screws. Install the three lower screws and make sure to tighten all screws
Enclosure Dimensions, pg.18).
2. The power supply is pre-wired to the ground (chassis). Connect main incoming ground to the provided green
grounding conductor lead. Connect unswitched AC power (115VAC 60Hz) to terminals marked [L, N] on both
powersupplyboards.Use14AWGorlargerforallpowerconnections.
Keep power-limited wiring separate from non power-limited wiring. Minimum .25” spacing must be provided
(Figs. 6-9, pgs. 13-16).
3. Select desired DC output voltage by setting SW1 to the appropriate position on the power supply board
(Maximal11D and Maximal33D), (Fig. 1, pg. 9). Maximal55D power supply is factory set at 12VDC.
Maximal77D power supply is factory set at 24VDC. Maximal75D consists of one (1) power supply board that is
factory set at 12VDC, and one (1) power supply board that is factory set at 24VDC.
4. Measure the output voltage of the unit before connecting any devices to ensure proper operation.
Improper or high voltage will damage these devices.
5. Output options (Fig. 2, pg. 9):
The unit will provide either sixteen (16) switched power outputs, sixteen (16) dry form “C” outputs, or any
combination of both switched power and form “C” outputs.