Altronix Maximal37E Data Sheet Manual do Utilizador

Consulte online ou descarregue Manual do Utilizador para Acessórios para eletricidade Altronix Maximal37E Data Sheet. Altronix Maximal37E Data Sheet User Manual Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 2
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 0
Maximal37E provides system designers and installers with “maximum” power choices
and the highest levels of versatility. It provides 12VDC, or 12VDC and 24VDC simulta-
neously via two (2) single output power supply/chargers. It includes AC fail, low battery
and battery presence monitoring. Optional Altronix
®
field installable sub-assemblies
provide multiple outputs and a wide range of features for specific Access Control and
Fire Alarm applications.
Maximal37E
Expandable Power System
Rev. DSMaximal37E - 06172013
Overview
Specifications
Input:
115VAC 60Hz, 10.0 amp input.
Output:
12VDC and/or 24VDC outputs.
Maximum output current:
Options P/S 1 P/S 2
A 12VDC @ 6 amp 24VDC @ 10 amp
B 24VDC @ 6 amp 24VDC @ 10 amp
Filtered and electronically regulated outputs (built-in
power supply).
Thermal and short circuit protection with auto reset.
Fuse Ratings:
Power Supply input fuse rated @ 3.5 amp/250V.
Features:
AC fail supervision (form “C” contact).
Low battery and battery presence supervision
(form “C” contact).
Battery Backup:
Built-in charger for sealed lead acid or gel type
batteries.
Automatic switch over to stand-by battery when
AC fails.
Battery Backup (cont’d):
Maximum charge current:
- AL600ULXB maximum charge current is 0.7 amp.
- AL1024ULXB maximum charge current is 3.6
amp.
Zero voltage drop when unit switches over to battery
backup (AC failure condition).
Visual Indicators:
AC input and DC output LED indicators.
Electrical:
Operating temperature: 0º C to 49º C ambient.
BTU/Hr.:
- 12VDC & 24VDC: 159.69 BTU/Hr.
- 24VDC: 196.54 BTU/Hr.
System AC input VA requirement: 1150VA.
Mechanical:
Enclosure Dimensions (H x W x D approx.):
26” x 19” x 6.25” (660.4mm x 482.6mm x 158.75mm)
Enclosure accommodates up to four (4)
12AH batteries.
Product weight (approx.): 42.3 lbs. (19.19 kg).
Shipping weight (approx.): 46.3 lbs. (21.00 kg).
Optional Field Installable UL Listed Sub Assembly Modules
Location A - ACM4, ACM4CB, MOM5, PD4UL, PD4ULCB,
PD8UL, PD8ULCB, PD16W & PD16WCB.
A
Power Supply
Power Supply
Stand-by
Battery
(optional)
Stand-by
Battery
(optional)
Stand-by
Battery
(optional)
Stand-by
Battery
(optional)
B
C
Location B - ACM4, ACM4CB, ACM8, ACM8CB, MOM5,
PD4UL, PD4ULCB, PD8UL, PD8ULCB, PD16W & PD16WCB.
Location C - ACM4, ACM4CB, ACM8, ACM8CB, MOM5,
PD4UL, PD4ULCB, PD8UL, PD8ULCB, PD16W & PD16WCB.
Maximal37E
Vista de página 0
1 2

Resumo do Conteúdo

Página 1 - Maximal37E

Maximal37E provides system designers and installers with “maximum” power choices and the highest levels of versatility. It provides 12VDC, or 12VDC an

Página 2 - Agency Approvals

Altronix Corp. - 140 58th Street, Brooklyn, NY 11220 • 718-567-8181 • 888-258-7669 • altronix.comEnclosure Dimensions (H x W x D approximate):26” x 19