Maximal33E provides system designers and installers with “maximum” power choices
and the highest levels of versatility. It provides 12VDC, 24VDC, or 12VDC and 24VDC
simultaneously via two (2) single output power supply/chargers. It includes AC fail, low
battery and battery presence monitoring. Optional Altronix
®
field installable sub-assem-
blies provide multiple outputs and a wide range of features for specific Access Control
and Fire Alarm applications.
Maximal33E
Expandable Power System
Rev. DSMaximal33E - 10312012
Overview
Specifications
Maximal33E
Input:
115VAC 60Hz, 7.0 amp input.
Output:
12VDC and/or 24VDC outputs.
Maximum output current:
Options P/S 1 P/S 2
A 12VDC @ 6 amp 12VDC @ 6 amp
B 24VDC @ 6 amp 24VDC @ 6 amp
C 12VDC @ 6 amp 24VDC @ 6 amp
Filtered and electronically regulated outputs (built-in
power supply).
Thermal and short circuit protection with auto reset.
Fuse Ratings:
Power Supply input fuse rated @ 3.5 amp/250V.
Features:
AC fail supervision (form “C” contact).
Low battery and battery presence supervision
(form “C” contact).
Battery Backup:
Built-in charger for sealed lead acid or gel type
batteries.
Battery Backup (cont’d):
Maximum charge current 0.7 amp per p/s board.
Automatic switch over to stand-by battery when
AC fails.
Zero voltage drop when unit switches over to battery
backup (AC failure condition).
Visual Indicators:
AC input and DC output LED indicators.
Electrical:
Operating temperature: 0º C to 49º C ambient.
BTU/Hr.:
- 12VDC: 73.70 BTU/Hr.
- 24VDC: 147.40 BTU/Hr.
- 12VDC & 24VDC: 110.55 BTU/Hr.
System AC input VA requirement: 805VA.
Mechanical:
Enclosure Dimensions (H x W x D approx.):
26” (660.4mm) x 19” (482.6mm) x 6.25” (158.75mm)
Enclosure accommodates up to four (4)
12AH batteries.
Product weight (approx.): 43.5 lbs. (19.73 kg).
Shipping weight (approx.): 47.5 lbs. (21.55 kg).
Optional Field Installable UL Listed Sub Assembly Modules
Location A - ACM4, ACM4CB, MOM5, PD4UL, PD4ULCB,
PD8UL, PD8ULCB, PD16W & PD16WCB.
A
Power Supply
Power Supply
Stand-by
Battery
(optional)
Stand-by
Battery
(optional)
Stand-by
Battery
(optional)
Stand-by
Battery
(optional)
B
C
Location B - ACM4, ACM4CB, ACM8, ACM8CB, MOM5,
PD4UL, PD4ULCB, PD8UL, PD8ULCB, PD16W & PD16WCB.
Location C - ACM4, ACM4CB, ACM8, ACM8CB, MOM5,
PD4UL, PD4ULCB, PD8UL, PD8ULCB, PD16W & PD16WCB.